WAYNE MEMORIAL HOSPITAL CAMPUS MEDICAL OFFICE BUILDING
SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING
Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
3. Pipe loops, offsets, and swing joints
A. ASTM A 269 - Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing
B. EJMA (STDS) - EJMA Standards; Expansion Joint Manufacturers Association.
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
1. Flexible Pipe Connectors: Indicate maximum temperature and pressure rating, face-to-face
length, live length and hose wall thickness.
2. Expansion Joints: Indicate maximum temperature and pressure rating, and maximum
C. Manufacturer's Instructions: Indicate manufacturer's installation instructions, special procedures,
D. Project Record Documents: Record installed locations of flexible pipe connectors, expansion
E. Maintenance Materials: Furnish the following for Owner’s use in maintenance of project.
1. See Section 01 60 00 – Product Requirements, for additional provisions
2. Extra Packing for Packed Expansion Joints: One set for each joint
EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING 12/22/11
WAYNE MEMORIAL HOSPITAL CAMPUS MEDICAL OFFICE BUILDING
Minnesota Flexible Corporation: www.minnesotaflexible.com
Substitutions: See Section 01 60 00 - Product Requirements
C. Exterior Sleeve: Double braided, stainless steel.
D. Pressure Rating: 150 psi and 450 degrees F.
G. Maximum offset: 3/4 inch on each side of installed center line.
H. Application: Steel piping installed outdoors or indoors.
FLEXIBLE PIPE CONNECTORS - COPPER PIPING
Minnesota Flexible Corporation: www.minnesotaflexible.com
Substitutions: See Section 01 60 00 - Product Requirements
D. Pressure Rating: 150 psi and 450 degrees F
G. Maximum Offset: 3/4 inch on each side of installed center line
H. Application: Copper piping, installed outdoors or indoors
EXPANSION JOINTS - STAINLESS STEEL BELLOWS TYPE
EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING 12/22/11
WAYNE MEMORIAL HOSPITAL CAMPUS MEDICAL OFFICE BUILDING
Minnesota Flexible Corporation: www.minnesotaflexible.com
Substitutions: See Section 01 60 00 - Product Requirements
B. Pressure Rating: 150 psi and 450 degrees F.
C. Maximum Compression: 1-3/4 inches unless indicated otherwise.
G. Application: Steel piping 3 inches and under.
EXPANSION JOINTS - EXTERNAL RING CONTROLLED STAINLESS STEEL BELLOWS TYPE
Minnesota Flexible Corporation: www.minnesotaflexible.com
Substitutions: See Section 01 60 00 - Product Requirements
B. Pressure Rating: 150 psi and 450 degrees F.
Application: Steel piping over 3 inches.
EXPANSION JOINTS - SINGLE OR DOUBLE SPHERE, FLEXIBLE COMPENSATOR
EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING 12/22/11
WAYNE MEMORIAL HOSPITAL CAMPUS MEDICAL OFFICE BUILDING
Minnesota Flexible Corporation: www.minnesotaflexible.com
Substitutions: See Section 01 60 00 - Product Requirements
B. Molded double arch spherical connector/expansion joint, manufactured with multiple plies of
nylon tire core fabric bonded within elastomer and reinforced with a spring steel wire.
C. Floating/rotatable flanges shall be zinc-coated steel and meet ANS 150# standard.
D. Pressure Rating: 150 PSIG at 250 degrees F.
E. Movement Capability: 1" compression, 3/4" extension; 1" offset, 30 degrees angular.
H. Application: Steel piping for hydronic service, 2 inches and over, installed indoors.
EXPANSION JOINTS - TWO-PLY BRONZE BELLOWS TYPE
Minnesota Flexible Corporation: www.minnesotaflexible.com
Substitutions: See Section 01 60 00 - Product Requirements
B. Construction: Bronze with anti-torque device, limit stops, internal guides.
C. Pressure Rating: 150 psi and 450 degrees F.
D. Maximum Compression: 1-3/4 inches unless otherwise indicated.
Substitutions: See Section 01 60 00 - Product Requirements
B. Pressure Rating: 150 psi and 400 degrees F
EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING 12/22/11
WAYNE MEMORIAL HOSPITAL CAMPUS MEDICAL OFFICE BUILDING
G. Application: Steel piping 10" diameter and under
H. Materials: Stainless steel hose and braid
Substitutions: See Section 01 60 00 - Product Requirements
D. Maximum Temperature: 650 degrees F (343 degree C)
H. Application: Steel piping 2 inches (50 mm) and over
Application: Steam and steam condensate piping
Minnesota Flexible Corporation: www.minnesotaflexible.com
Substitutions: See Section 01 60 00 - Product Requirements.
Two piece welded steel with enamel paint, bolted, with spider to fit standard pipe, frame with four mounting holes, clearance for the specified thickness insulation, minimum 3 inches travel.
EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING 12/22/11
WAYNE MEMORIAL HOSPITAL CAMPUS MEDICAL OFFICE BUILDING
Minnesota Flexible Corporation: www.minnesotaflexible.com
Substitutions: See Section 01 60 00 - Product Requirements.
Fabricated steel, bronze, ductile iron, or cast steel body, double ball bearing race, field lubricated, with rubber (Buna-N) o-ring seals.
A. Install in accordance with manufacturer's instructions.
B. Install in accordance with EJMA (Expansion Joint Manufacturers Association) Standards.
C. Install flexible pipe connectors on pipes connected to vibration isolated equipment. Provide line
D. Install flexible connectors at right angles to displacement. Install one end immediately adjacent to
isolated equipment and anchor other end. Install in horizontal plane unless indicated otherwise.
E. Anchor pipe to building structure where indicated. Provide pipe guides so movement is directed
along axis of pipe only. Erect piping such that strain and weight is not on cast connections or apparatus.
Provide support and equipment required to control expansion and contraction of piping. Provide loops, pipe offsets, and swing joints, or expansion joints where required.
EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING 12/22/11
Management of Neuromuscular Diseases - Letter 9 Symptomatische Therapie der Amyotrophen Lateralsklerose - 1. Teil Muskelschwäche, Spastik, Muskelkrämpfe Weiterführende Literatur Einleitung Die Amyotrophe Lateralsklerose (ALS) ist die häufigste degenerative Erkrankung des motorischenSystems. Auch wenn mit Riluzol [Rilutek®] inzwischen wenigstens ein Medikament zur Verfügung steht,das ei
Technisches Merkblatt Holzschutzsysteme impranol -Holzschutzgrund Lösemittelhaltige, farblose Grundierung zum Schutz von Holz im Au- ßenbereich ohne Erdkontakt vor Bläue, holzzerstörenden Insekten und Pilzen. RAL-Gütesiegel, Verleihungsurkunde-Nr. 728 Anwendungs- impranol®-Holzschutzgrund dient dem Schutz statisch nicht beanspruchter Hölzer ohne Erdkontakt im Au